高阻燃
電力電纜
產(chǎn)品標(biāo)準(zhǔn) Standard
本產(chǎn)品按GB12706-91《額定電壓35kV及以下銅芯、鋁芯塑料絕緣電力電纜》、GB12666.5-90《電線電纜成束燃燒試驗(yàn)》、GB/T17650-1998《取自電纜或光纜的材料燃燒時(shí)釋出氣體的試驗(yàn)方法》和GB/T17651-1998《電纜或光纜在特定條件下燃燒的煙密度測定》標(biāo)準(zhǔn)生產(chǎn)0.6/1kV-26/35kV塑料絕緣電力電纜,同時(shí)還可根據(jù)用戶需要按國際電工委員會(huì)推薦標(biāo)準(zhǔn)IEC、英國標(biāo)準(zhǔn)、德國標(biāo)準(zhǔn)及美國標(biāo)準(zhǔn)生產(chǎn)。
The product is manufactured according to the standard of GB12706-91、GB12666.5-90、GB/T17650-1998 and GB/T17651-1998 or IEC and DIN and ICEA.
適用范圍 Applications
本產(chǎn)品適用于工頻額定電壓0.6/1kV-26/35kV 輸配電線路作配送電能之用。
The product is suitable for power transmission and distribution lines with rated voltage 0.6/1kV-26/35kV.
使用特性 Operating characteristics .
工頻額定電壓U0/U為0.6/1kV-26/35kV.
Rated power frequency voltage U0/U:0.6/1kV-26/35kV.
PVC絕緣電纜導(dǎo)體的長期最高工作溫度為70℃。XLPE絕緣電纜導(dǎo)體的長期允許最高工作溫度為90℃
PVC insulated power cable Max . permissible continuous operating temperature of the conductor should not exceed 70 ℃,XPLE permissible continuous operating temperature of the conductor should not exceed 90℃.
短路時(shí)(最長持續(xù)時(shí)間不超過5s)電纜導(dǎo)體的最高溫度不超過250
Max Short –circurrt temperature of conductor shall not exceed 250.(5s maximum duration)
電纜敷設(shè)時(shí)環(huán)境溫度不低于0℃
The installation temperature should not below 0℃
電纜阻燃性能滿足GB12666.5-90標(biāo)準(zhǔn)A類相應(yīng)指標(biāo)要求。
The flame-ratardant properties of cable comply with the requirements specified in A kind of GB12666.5-90
低鹵電纜除應(yīng)滿足GB12666.5-90標(biāo)準(zhǔn)中A類相應(yīng)指標(biāo)要求外,還應(yīng)滿足GB/T17650.1-1998標(biāo)準(zhǔn)規(guī)定的相應(yīng)指標(biāo)。
The flame-retardant properties of lower halogen cable comply with requirements specified in A kind of GB12666.5-90 except compluing with requirements specified in GB/T17650.2-1998 .
無鹵電纜除應(yīng)滿足GB12666.5-90標(biāo)準(zhǔn)中A類相應(yīng)指標(biāo)要求外,還應(yīng)滿足GB/T17650.2-1998和GB/T17651-1998標(biāo)準(zhǔn)規(guī)定的相應(yīng)指標(biāo)。
The flame-retardant properties of no halogen cable comply with requirements specified in A kind of GB12666.5-90 except compluing with requirements specified in GB/T17650.2-1998 .and GB/T17651-1998.
電纜彎曲半徑:三芯電纜不小于電纜外徑15倍;單芯電纜不小于電纜外徑20倍。
Three bending radius of a single core should not less than 20 times of the cable diameter
Two bending radius of a three-core cable should not less than 15 times of the cable diameter.
電纜額定電壓的選擇 Voltage designation
電纜額定電壓應(yīng)適合于電纜的系統(tǒng)的運(yùn)行狀況,用U0/U(Um)表示,均為有效值,單位為kv
U0- 電纜設(shè)計(jì)用導(dǎo)體與屏蔽或金屬套之間的額定工作電壓;
U—電纜設(shè)計(jì)用導(dǎo)體之間的額定工頻電壓;
Um –設(shè)備可承受的“最高系統(tǒng)”電壓的最大值。
The rated voltage of the cable for a given application shall be suitable for the operating condition in the system in which the cable is used , and is expressed in the form of U0/U(Um)are applied to the system voltages and running state , and expressed in the form U0/Ukv.
U0-The rated power-frequency voltage between conductor and earth or metallic screen ,for which the cable designed .
U-The rated power –frequency voltage between conductors for which the cable designed.
Um- –The maximum value of “the highest system voltage ”for which the equipment may be used.
三相系統(tǒng)用電纜的U0值推薦如下表:
The values U0 recommended for cables to be used in three-phase systems are listed below:
第一類——用于單相接地故障時(shí)間每一次一般不大于1min,亦可用于最長不超過8小時(shí),每年累計(jì)不超過125小時(shí)的系統(tǒng)。
第二類——用于接地故障時(shí)間更長的系統(tǒng)及對(duì)電纜絕緣性能要求較高的場合。
The first class cable – suitable for one single –phase earthing – block time does not exceed one minute each time. Max. time not exceed 8 hours ,and not exceed 125 hours in all in one year.
The second class cable – suitable for more the earthing – block time and more better insulated performa. 電纜的型號(hào) Type of cable 0.6/1kv高阻燃(隔氧層)電纜的生產(chǎn)范圍
Production Range of high performance flame –retardant cable 1.8/3~26/35kv高阻燃(隔氧層)電纜的生產(chǎn)范圍
Production Range of high performance flame- retardant cable
阻燃電纜型號(hào)規(guī)格
型號(hào) Type |
芯數(shù) cores |
電壓 Rated voltage kV |
銅芯 Copper conductor |
鋁芯 Aluminum conductor |
1.8/3 |
3.6/6 6/6 |
6/10 8.7/10 |
8.7/15 ~12/20 |
18/30 ~26/35 |
標(biāo)稱截面 Nominal Cross-section Mm2 |
GZR-YJV GZR-DL(WL)-YJV GZR-YJV22 GZR-DL(WL)-YJV22 GZR-YJV32 GZR-DL(WL)-YJV32 |
GZR-YJLV GZR-DL(WL)-YJLV GZR-YJLV22 GZR-DL(WL)-YJLV22 GZR-YJLV32 GZR-DL(WL)-YJLV32 |
1 |
10~630 10~630 10~630 |
25~630 25~630 25~630 |
25~630 25~630 25~630 |
35~630 35~630 35~630 |
35~630 35~630 35~630 |
GZR-YJV GZR-DL(WL)-YJV GZR-YJV 22 GZR-DL(WL)-YJV22 GZR-YJV 32 GZR-DL(WL)-YJV32 |
GZR-YJLV GZR-DL(WL)-YJLV GZR-YJLV 22 GZR-DL(WL)-YJLV22 GZR-YJLV 32 GZR-DL(WL)-YJLV32 |
3 |
10~500 10~500 10~500 |
25~500 25~500 25~500 |
25~500 25~500 25~500 |
35~500 35~500 35~500 |
35~500 35~500 35~500 |
注:單芯鎧裝型高阻燃(隔氧層)電纜僅用于直流系統(tǒng),應(yīng)采用非磁性材料的鎧裝層或采用隔磁措施。
Note: The single-core armoured high performance flame-retardant cables are used for d.c system only, as for a . c. system non-magnetic aromour materials should be or magnetic isolation should be applied. 載流量計(jì)算條件:
Current ratings are calculated for the following installation conditions:
導(dǎo)體最高工作溫度 Max. Rated temperature of the cable conductor
聚氯乙烯絕緣為70℃,交聯(lián)聚乙烯絕緣為90℃
PVC insulated 70℃ ,XPLE insulated 90℃
環(huán)境空氣溫度:
Ambient air temperature 40℃
土壤溫度:
soil temperature 25℃
土壤熱阻系數(shù):
Rating factors for ground thermal resistive 1.0. ℃ m/w
埋設(shè)深度: Depth 0.8m
僅考慮一個(gè)回路 Single circuit parallel laid
單芯電纜為水平敷設(shè),間距為一個(gè)電纜外徑
Single core is paralleled installation .Adjacent space is equivalent to the diameter of cable.
環(huán)境條件對(duì)電纜載流量的修正系數(shù)
Rating factors of current rating for ambient condition
土壤敷設(shè) Direct in ground
不同土壤溫度下載流量修正系數(shù) Rating factors of current rating for ambient temperature